Products Recorders
TESLA 4000 Power System Recorder with CDR, PMU and IEC 61850 process and station bus protocols
Model 4000-SV
Recording for a fully digital substation environment
|
TESLA 4000 SV supports both IEC 61850-9-2 LE as well as IEC 61869-9 to subscribe to Sampled Value streams from Merging Unit. It also publishes and subscribes to GOOSE messages from protective relays and switchgear. The Model 4000-SV also supports direct streaming of MMS reports to remote clients, eliminating the need for RTUs. The Model 4000-SV supports the top-down or bottom-up engineering process defined in the IEC 61850-6 standard which enables standardization and interoperability of fault and disturbance recording solutions as the industry moves towards fully digital substations.
Applications
- Complete integrated insight of power system health
- Performance monitoring of substation IEDs and equipment
- Over 1000 user settable triggers capture vital information that could be missed by relays in the system
- Information provided for wide area monitoring (WAMS) and analysis
- As a PMU, streams up to 36 phasors, 24 analog quantities, and 320 digital statuses simultaneously
|
 |
|
Features and Benefits
- Easy-to-use setting and analysis software
- GOOSE subscription and publishing on any port
- IEC 61850 Edition 2 and IEC 61869-9 support
- CDR meets NERC PRC-002 and 028 DME standards
- Support for PRP network redundancy protocol on multiple ports, up to 3 redundancy pairs
- Support for GOOSE subscription from different data types including Boolean, Dbpos, Health, Int32
- Time synchronization is supported via legacy IRIG-B or Precision Time Protocol (PTP); PTP is fully compliant with applicable power and utility industry profiles
- Circular sequent of events report buffer of 1000 events
- Sampling rate configurable at 80 or 256 s/c for IEC61850 9-2 stream and 4000, 4800, 14400 Hz for IEC 61869-9 SV stream
- Recording of logic channels in fault and swing recordings
- IEEE C37.118-2014 and IEEE/IEC 60255-118-1:2018 compliant
- Swing (Slow) records with a sampling rate of 1 or 2 s/c
- Standard storage memory 64GB with 1 TB option
Benefits of IEC 61850 / IEC 61869-9 SV-Based Fault and Disturbance Recording System
- Savings on costly wiring runs from instrument transformers (located in substation yards) to conventional DFRs located in substation control house
- Absence of open CT secondary improves operational safety
- Ease of commissioning, future modification, and expansion
- Interoperability of DFR systems and protective relaying systems using common measurements available from merging units
Learn more about:
|
|
|
|