The F-PRO provides
comprehensive single breaker or ring configured
feeder protection, reclosing, metering, trend recording,
fault recording & monitoring in one integrated
platform.
Protection
Comprehensive overcurrent & recloser functions;
over/under frequency, fixed level or rate of change
(df/dt), provides up to 4 stages of load shedding
& inter-tie protection.
Protection functions include IEEE devices 50LS,
50BF, 50/51/67, 50N/51N/67, 46/50/51/67, 25/27/59,
21P, 27, 32, 59, 60, 79, 81, THD.
ProLogic
control logic statements.
8 setting groups available with 16 group logic
statements for adaptive relay setting.
Recording, Monitoring
& Metering
High quality recording
- fault recording (96 samples/cycle), trend &
event logging (1 ms resolution).
Separate breaker monitoring of each feeder breaker
using breaker logic & I*I*t functions.
Demand, Peak Demand & Energy metering features
with complete SCADA metering (DNP or Modbus).
Front display, Event Log, fault location, MW,
MVAR, volts, amps, power factor, frequency, THD
& Peak Demand & Energy.
Trend recording with minimum 30-day capacity.
Fault locator.
Substation Automation
- Ethernet Ready
Direct-connect DNP3 & Modbus SCADA communication
protocols.
3 RS-232 communication ports.
IRIG-B time stamping & sample synchronization.
30 virtual inputs with complete SCADA metering
& DNP control.
Easy to use, simplified relay setting & record
analysis software (Windows? 9x/ME/NT/2000).
Intuitive ASCII-terminal interface for full local
or remote access. |
|
Bus
Relay Feeder
Relay Transmission
Line Relay Transformer
Relay |